Vision-60 System Technical DataInstallation Requirements
- Pyrobel-60-25 glazing provided with arris cut at butt edge of glass
- Space between glazing panels not to exceed 4mm
- Dow Corning 745s neutral silicone (or other 100% pure silicone) caulking to be pressure-glazed at butt joints only and cured for a minimum of 30 days
- Pyrobel must be glazed with 3/16" x 1-1/4" closed cell foam glazing tape with neutral cure silicone around the perimeter of both sides of glass (perimeter silicone must not be pressure glazed)
- PEMKO 3000S45 intumescent tape to be applied at the top stops in addition to closed cell foam tape (apply PEMKO tape on top of close cell foam tape to form two layers of tape)
- Perimeter framing to be either Quick-Frame or StileLite systems with 1-1/2" stop height.
- Pyrobel panels may be glazed either horizontally or vertically, but not stacked.
- Decorative profiles may be added to the face of the glass without affecting the performance of the system.
Due to the complex nature of this wall system, glazing instructions must be followed explicitly in order to maintain the manufacturer's guarantee. Specifications and details can be downloaded from this site.
|