DOORS |
BORROWED LITES |
TRANSOMS AND RAISED SIDELITES |
| Width |
36" |
82 3/8" |
41 1/2" |
| Height |
61" |
82 3/8" |
41 1/2" |
| Square Inches (Max.) |
2196" |
3418.5" |
1286.5" |
| Stop Height |
5/8" |
5/8" |
5/8" |
Listings Testing completed by Intertek Testing
Services Warnock-Hersey certification with ASTM E-119, E-152, E-163,
CAN 4S-104, 106, NFPA-251, 257, 263, UBC 7-1, 7-2, 7-4 (1997), UL-9,
UL-10C. Test report number WHI PSV-1419 and WHI 495-1681. |
Labeling All product is permanently labeled bearing
the manufacturers name, testing laboratory, rating and safety
standards. |
Specifications All 90 minute fire-rated and impact
safety rated glass shall be designated on the drawings as Pyrobel-90-35,
90 minute fire and safety glazing. |
| SINGLE |
SINGLE EXTERIOR |
INSULATED EXTERIOR |
| Thickness |
1
3/8" (35mm) +2/-2mm |
1
1/2" (37mm) +2/-2mm |
2
1/8" (55mm) +2/-2mm |
| Weight (per sq. ft) |
16.4 lbs/sq. ft. (80kg/ sq. m2) |
18 lbs/sq. ft. (88kg/ sq. m2) |
21 lbs/sq. ft. (103 kg/ sq. m2) |
| Light Transmission |
82% |
81% |
72% |
| Sound Reduction |
Rw= 43 dB |
Rw= 44 dB |
Rw= 46 dB |
| Safety Rating | CPSC 16CFR1201 Cat. II, 400 ft. lbs. ANSI
Z97.1 |
| Fire Rating | 90 minutes |
90 minutes |
90 minutes |
| R-Value | 1.16 |
1.21 |
2.22 |
| U-Value | 0.862 |
0.828 |
0.460 |
| Maximum structural load performance (wind loadASTM E330) of
Pyrobel-90-37 is 512.4 lbs./sq. ft. |
Quality Standard Pyrobel products are specially
prepared products designed to prevent the expansion of fire. Thus, the
specific optical quality should not be compared to single float or
laminated pvb glazing. Consult InterEdge for specific acceptable quality
standards before purchase. |
Guarantee Manufacturer, (AGC Flat Glass Europe) guarantees
the characteristics of Pyrobel for a period of 5 years from date of
delivery. Due to the nature of its interlayers, Pyrobel may develop some
minor imperfections such as small bubbles or a slight distortion which
will not affect the free vision through the glazing or fire performance.
A variation of up to 5% of light transmission or haze shall not be
considered a defect. This guarantee is for replacement of glass only and
any other costs associated with the removal or replacement of defective
units are not the responsibility of the manufacturer. The guarantee
shall apply only to glass handled, transported, stored and installed in
accordance with normal procedures. |